Back to the product list

HSH Series HeatSink™

2,000-3,000 SCFM

HSH Series HeatSink dryers include the newest design innovations and operating efficiencies from ZEKS. Energy savings result from True-Cycling™ operation which cycles the dryer refrigeration system in response to compressed air demand, while an advanced control system optimizes dryer performance.

In response to compressed air system demand, the dryer refrigeration system automatically cycles on and off to cool a thermal storage media. This media is circulated through a multi-layer heat exchanger, thereby cooling the compressed air and delivering dry air to the compressed air system. Condensed moisture is efficiently removed from the air stream through a multi-drain system.

3 Models, 2,000-3,000 SCFM

  • 2,000–3,000 SCFM capacity range
  • Thermal Mass (cycling) refrigeration system

  • Low-GWP R454B refrigerant
  • Proprietary heat exchanger design
  • Integrated pre-filter
  • Consistent Class 4 pressure dew point performance
  • Compact, packaged system design

ZEKS Models

Capacity
SCFM*

# of
Modules

Overall Dimensions**

Ship
Weight**
LBS.

In/Out Air
Connect
Size

Operating
kW***

Refrigerant
Type

Max
Working
Pressure

Voltage

W
IN.

D
IN.

H
IN.

AC

WC

2000HSH

2000

1

33.9

90.4

95.8

3398

6" FLG

9.60

6.70

R454B

200 PSIG

460/3/60

2400HSH

2400

1

33.9

90.4

95.8

3419

6" FLG

12.30

7.60

R454B

200 PSIG

460/3/60

3000HSH

3000

1

33.9

90.4

95.8

3560

6" FLG

15.30

10.10

R454B

200 PSIG

460/3/60

4000HSHM

4000

2

80.8

98.6

97.8

6937

8" FLG

19.30

13.60

R454B

200 PSIG

460/3/60

4800HSHM

4800

2

80.8

98.6

97.8

6979

8" FLG

24.70

15.40

R454B

200 PSIG

460/3/60

6000HSHM

6000

2

80.8

98.6

97.8

7572

8" FLG

30.70

20.30

R454B

200 PSIG

460/3/60

7200HSHM

7200

3

114.9

100.0

103.9

10124

10" FLG

36.90

23.00

R454B

200 PSIG

460/3/60

9000HSHM

9000

3

114.9

100.0

103.9

12194

10" FLG

46.00

30.40

R454B

200 PSIG

460/3/60

12000HSHM

12000

4

149.2

100.2

105.5

16682

14" FLG

61.30

40.40

R454B

200 PSIG

460/3/60

15000HSHM

15000

5

179.4

100.2

105.5

19624

14" FLG

76.60

50.50

R454B

200 PSIG

460/3/60

18000HSHM

18000

6

217.3

100.2

106.5

23081

14" FLG

91.80

60.60

R454B

200 PSIG

460/3/60

21000HSHM

21000

7

251.3

100.2

106.5

27365

14" FLG

107.10

70.60

R454B

200 PSIG

460/3/60

24000HSHM

24000

8

285.4

100.2

106.5

31661

14" FLG

122.40

80.70

R454B

200 PSIG

460/3/60

 

*Performance based on ISO 7183, Table 2, Option A2 (100 PSIG Inlet Air Pressure; 100 F Inlet Air Temperature; 100 F Ambient Air Temperature; 100% Relative Humidity)

**Overall dimensions & shipping weights are for air cooled models. Consult engineering datasheets for water cooled data.

***Average kilowatts per hour of dryer operation at full rated capacity. AC = Air Cooled; WC = Water Cooled. NEMA 1 electrical, standard